CHAPTER 5 PARAMETERS
Expansion Mode
Standby sequence reset method
• Selects the conditions for enabling reset after the standby sequence of the alarm
has been canceled.
• Condition A:
Function
Control started (including power ON), and, alarm value, input shift value or set
point (except for changing SP mode or during Remote SP) changed.
• Condition B:
Power ON
• The following illustration shows an operation example for the lower-limit alarm
with standby sequence.
(after change)
Alarm Output: Condition A
Alarm Output: Condition B
0: Condition A / 1: Condition B
Comment
F Related parameters
"Alarm 1 type" "Alarm 2 type" "Alarm 3 type" (setup mode)
See
Automatic return of display mode
• If you do not operate any of the controller keys for the time set in this parameter
when in levels 0 to 2 modes, the display automatically returns to the PV/SP dis-
play.
Function
• When this parameter is set to "0", this function is disabled. (The screen will not
change automatically.)
• This parameter is invalid while the menu is displayed.
Comment
5--34
SP value change
Alarm point
Alarm point
Setting Range
Setting Range
0 to 99
Second
Condition A only
Condition A only
Default
0
Unit
Default
0
Alarm hysteresis
f : Standby sequence release point
F : Standby sequence restart point