CHAPTER 5 PARAMETERS
Option Mode
Remote SP upper limit
Remote SP lower limit
• Sets the remote SP upper and lower limit values. The upper limit value is equiva-
lent to 20 mA, and the lower limit value is equivalent to 4 mA. Set the upper limit
value in the "remote SP upper limit" parameter and the lower limit value in the
Function
"remote SP lower limit" parameter.
• When the "SP setting upper limit" and "SP setting lower limit" parameters are
changed, the remote SP upper and lower limit values are forcibly changed to the
SP setting upper and lower limit values.
Remote SP upper limit
Remote SP lower limit
Comment
F Related article
4.3 How to Use the Remote SP (page 4-7)
F Related parameters
See
"Decimal point" (setup mode)
"SP setting upper limit" "SP setting lower limit" (expansion mode)
"Remote SP enable" (option mode)
5--40
RSP
Upper limit value
Lower limit value
Parameter
SP setting lower limit to SP setting upper limit
SP setting lower limit to SP setting upper limit
Conditions of Use
The remote SP function must be enabled.
4
20
Setting Range
Input (mA)
Unit
Default
EU
1300
EU
-200