Com - Omron CJ - 09-2009 Operation Manual

Programmable controllers
Table of Contents

Advertisement

Specifications of Basic I/O Units
• Set the pulse width of signals input to the Interrupt Input Unit so they satisfy the above conditions.
Terminal Connections
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
CJ1W-IDP01 Quick-response Input Unit (16 Points)
Temperature characteristics for simultaneously ON points
Input voltage: 26.4 V DC
Ambient temperature
0
A0
1
B0
2
A1
3
B1
4
A2
5
B2
6
A3
7
B3
8
A4
9
B4
10
A5
11
B5
12
A6
13
B6
14
A7
15
B7
C O M
A8
C O M
B8
The polarity can be connected in either direction.
Rated Input Voltage
Rated Input Voltage Range
Input Impedance
Input Current
ON Voltage/ON Current
OFF Voltage/OFF Current
ON Response Time
OFF Response Time
Number of Circuits
Number of Simultaneously
ON Points
Insulation Resistance
Dielectric Strength
Internal Current Consumption 5 V DC: 80 mA max.
Weight
Accessories
16 points at 45°C.
12 points at 55°C.
24 V DC
24 V DC
20.4 to 26.4 V DC
3.3 kΩ
7 mA typical (at 24 V DC)
14.4 V DC min./3 mA min.
5 V DC max./1 mA max.
0.05 ms max.
0.5 ms max.
16 (16 points/common)
100% simultaneously ON (24 V DC)
20 MΩ between external terminals and GR terminal
(at 100 V DC)
1,000 V AC between external terminals and GR ter-
minal for 1 minute at a leakage current of 10 mA
max.
110 g max.
None
Appendix A
551

Advertisement

Table of Contents
loading

Table of Contents