PLC Setup
Execute Process
Detect Low Battery
Programming
Console address
Word
Bit(s)
+128
15
0: Detect
1: Do not detect
Default: 0
Detect Interrupt Task Error
Programming
Console address
Word
Bit(s)
+128
14
0: Detect
1: Do not detect
Default: 0
Stop CPU on Instruction Error (Instruction Error Operation)
Programming
Console address
Word
Bit(s)
+197
15
0: Continue
1: Stop
Default: 0
Do Not Register FAL to Error Log
Programming
Console address
Word
Bit(s)
+129
15
0: Record user-
defined FAL errors
in error log.
1: Don't record user-
defined FAL errors
in error log.
Default: 0
Settings
This setting determines whether CPU Unit
battery errors are detected. If this setting is
set to 0 and a battery error is detected, the
ERR/ALM indicator on the CPU Unit will
flash and the Battery Error Flag (A40204)
will be turned ON, but CPU Unit operation
will continue.
Settings
This setting determines whether interrupt
task errors are detected. If this setting is set
to 0 and an interrupt task error is detected,
the ERR/ALM indicator on the CPU Unit will
flash and the Interrupt Task Error Flag
(A40213) will be turned ON, but CPU Unit
operation will continue.
Settings
This setting determines whether instruction
errors (instruction processing errors (ER)
and illegal access errors (AER)) are treated
as non-fatal or fatal errors. When this setting
is set to 1, CPU Unit operation will be
stopped if the ER or AER Flags is turned
ON (even when the AER Flag is turned ON
for an indirect DM/EM BCD error).
Related Flags: A29508 (Instruction Pro-
cessing Error Flag)
A29509 (Indirect DM/EM BCD Error Flag)
A29510 (Illegal Access Error Flag)
Settings
This setting determines if user-defined FAL
errors created with FAL(006) and time moni-
toring for FPD(269) will be recorded in the
error log (A100 to A199). Set it to 1 so pre-
vent these errors from being recorded.
Note This setting does not exists in CJ1@-CPU@@ CPU Units.
Function
Function
Function
Function
Section 7-1
Related
When set-
flags and
ting is read
words
by CPU Unit
A40204 (Bat-
At the next
tery Error
cycle.
Flag)
Related
When set-
flags and
ting is read
words
by CPU Unit
A40213
At the next
(Interrupt
cycle.
Task Error
Flag)
Related
When set-
flags and
ting is read
words
by CPU Unit
A29508,
At start of
A29509,
operation.
A29510
(If this setting
is set to 0,
these flags
won't be
turned ON
even if an
instruction
error occurs.)
Related
When set-
flags and
ting is read
words
by CPU Unit
---
Whenever
FAL(006) is
executed
(every cycle).
291