Specifications of Basic I/O Units
Circuit Configuration
Terminal Connections
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
CJ1W-OA201 Triac Output Unit (8 Points)
Output indicator
2 A 250 V AC,
2 A 24 V DC max.
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Number of Circuits
Surge Protector
Fuses
Insulation Resistance
Dielectric Strength
Internal Current Consumption
Weight
Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used
for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O
tables.
to
0.6 A 250 V AC, 50/60 Hz (2.4 A/Unit)
15 A (pulse width: 10 ms)
50 mA 75 V AC
1.5 mA (200 V AC) max.,
1.6 V AC max.
1 ms max.
1/2 of load frequency+1 ms or less.
8 (8 points/common)
C.R Absorber + Surge Absorber
5 A (1/common, 1 used)
The fuse cannot be replaced by the user.
20 MΩ between the external terminals and the GR
terminal (500 V DC)
2,000 V AC between the external terminals and
the GR terminal for 1 minute at a leakage current
of 10 mA max.
220 mA max.
150 g max.
Appendix A
567