Specifications of Basic I/O Units
Circuit Configuration
When the output current of any output exceeds the detection current, the output for that point will turn OFF. At
the same time, the ERR indicator will light and the corresponding flag (one for each common) in the Basic I/O
Unit Information Area (A050 to A069) will turn ON.
582
ON Response Time
OFF Response Time
Load Short-circuit Prevention
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current Consumption
External Power Supply
Weight
Accessories
Note The maximum load currents will be 2.0 A/common and 4.0 A/Unit if a
pressure-welded connector is used.
Output indicator
ERR indicator
0.5 ms max.
1.0 ms max.
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance. (Refer to
page 590.)
20 MΩ between the external terminals and the GR
terminal (100 V DC)
1,000 V AC between the external terminals and the
GR terminal for 1 minute at a leakage current of
10 mA max.
32 (16 points/common, 2 circuits)
5 V DC 150 mA max.
20.4 to 26.4 V DC, 70 mA min.
80 g max.
None
I/O word "m"
to
I/O word "m+1"
to
Appendix A