Omron CJ - 09-2009 Operation Manual page 448

Programmable controllers
Table of Contents

Advertisement

Auxiliary Area
Memory Error Information
Name
Memory Error Flag
(Fatal error)
Memory Error Location
Startup Memory Card Transfer
Error Flag
Flash Memory Error
(Not supported by CJ1@-
CPU@@ CPU Units.)
PLC Setup Error Information
Name
PLC Setup Error Flag
(Non-fatal error)
PLC Setup Error Location
400
Address
A40115
ON when an error occurred in memory or there was an error
in automatic transfer from the Memory Card when the power
was turned ON.
The ERR/ALM indicator on the front of the CPU Unit will light
and CPU Unit operation will stop when this flag turns ON.
If the automatic data transfer at startup fails, A40309 will be
turned ON. If an error occurs in automatic transfer at startup,
this error cannot be cleared.
A40300 to
When a memory error occurs, the Memory Error Flag
A40308
(A40115) is turned ON and one of the following flags is
turned ON to indicate the memory area where the error
occurred.
A40300: User program
A40304: PLC Setup
A40305: Registered I/O Table
A40307: Routing Table
A40308: CJ-series CPU Bus Unit Settings
A40309
ON when an error occurs in automatically transferring a file
from the Memory Card to the CPU Unit at startup, including
when a file is missing or a Memory Card is not mounted.
The error can be cleared by turning OFF the power. (This
error cannot be cleared while the power is ON.)
A40310
Turns ON when the flash memory fails.
Address
A40210
ON when there is a setting error in the PLC Setup.
A406
When there is a setting error in the PLC Setup, the location
of that error is written to A406 in 16 bits binary. The location
is given as the address set on the Programming Console.
Description
Description
Section 9-11
Access
Read-only
Read-only
Read-only
Read-only
Access
Read-only
Read-only