Error Processing
Error
Program-
ming
code (in
Console
display
Unit/Rack
UNIT No.
80E9
Number
DPL ERR
Duplica-
tion error
RACK No.
80EA
DPL ERR
Program
PRO-
80F0
error
GRAM
ERR
Error
Flag and
word data
A400)
A40113:
The same number has been
Duplication
allocated to more than one
Error Flag
CPU Bus Unit.
Bits A41000 to A41015 corre-
A410: CPU
spond to unit numbers 0 to F.
Bus Unit
Duplicate
Number
Flags
A40113:
The same number has been
Duplication
allocated to more than one
Error Flag
Special I/O Unit.
Bits A41100 to A41615 corre-
A411 to
spond to unit numbers 0 to
A416: Spe-
95.
cial I/O Unit
Duplicate
Number
Flags
A409:
The same I/O word has been
Expansion
allocated to more than one
Rack Dupli-
Basic I/O Unit.
cate Rack
Number
An Expansion Rack's starting
word address exceeds CIO
0901.
The corresponding bit in
A40900 to A40903 (Racks 0
to 3) will be turned ON.
A40109:
The program is incorrect. See
Program
the following rows of this table
Error Flag
for details.
A294 to
The address at which the pro-
A299: Pro-
gram stopped will be output
gram error
to A298 and A299.
information
A29511: No END error
A29515: UM overflow error
The last address in UM (user
program memory) has been
exceeded.
Probable cause
Check the unit numbers, eliminate the
duplications, and turn the Rack's power
supply OFF and then ON again.
Check the unit numbers, eliminate the
duplications, and turn the Rack's power
supply OFF and then ON again.
Check allocations to Units on the rack
number whose bit in ON in A40900 to
A40903. Correct the allocations so that
no words are allocated more than once,
including to Units on other Racks, and
turn the Rack's power supply OFF and
then ON again.
Check the first word setting for the Rack
indicated in A40900 to A40903 and
change the setting to a valid word
address below CIO 0900 with a Pro-
gramming Device.
Check A295 to determine the type of
error that occurred and check A298/
A299 to find the program address where
the error occurred.
Correct the program and then clear the
error.
Be sure that there is an END(001)
instruction at the end of the task speci-
fied in A294 (program stop task num-
ber). The address where the END(001)
Use a Programming Device to transfer
the program again.
Section 11-2
Possible remedy
509