Error Processing
Error
Program-
ming
Console
display
Basic I/O
DENSITY
error
I/O ERR
PLC Setup
PLC Setup
error
ERR
CPU Bus
CPU BU
Unit error
ERR
Special I/O
SIOU ERR 0300 to
Unit error
Battery
BATT
error
LOW
Error
Flag and
code (in
word data
A400)
009A
A40212:
An error has occurred in a
Basic I/O
Basic I/O Unit.
Unit Error
A408 contains the errant
Flag
rack/slot number.
A408: Basic
I/O Unit
Error, Slot
Number
009B
A40210:
There is a setting error in the
PLC Setup
PLC Setup. The location of
Error Flag
the error is written to A406.
A406: PLC
Setup Error
Location
0200 to
A40207:
An error occurred in a data
020F
CPU Bus
exchange between the CPU
Unit Error
Unit and a CPU Bus Unit.
Flag
The corresponding flag in
A417: CPU
A417 is turned ON to indi-
Bus Unit
cate the problem Unit. Bits
Error, Unit
A41700 to A41715 corre-
Number
spond to unit numbers 0 to F.
Flags
A40206:
An error occurred in a data
035F, or
Special I/O
exchange between the CPU
03FF
Unit Error
Unit and a Special I/O Unit.
Flag
The corresponding flag in
A418 to
A418 to A423 is turned ON
A423: Spe-
to indicate the problem Unit.
cial I/O Unit
Bits A41800 to A42315 cor-
Error, Unit
respond to unit numbers 0 to
Number
95.
Flags
00F7
A40204:
This error occurs when the
Battery
PLC Setup has been set to
Error Flag
detect battery errors and the
CPU Unit's backup battery is
missing or its voltage has
dropped.
Probable cause
Check the errant Unit for blown fuse, etc.
Change the indicated setting to a valid
setting.
Check the Unit indicated in A417. Refer
to the Unit's operation manual to find
and correct the cause of the error.
Restart the Unit by toggling its Restart
Bit or turn the power OFF and ON again.
Replace the Unit if it won't restart.
Check the Unit indicated in A418 to
A423. Refer to the Unit's operation man-
ual to find and correct the cause of the
error. Restart the Unit by toggling its
Restart Bit or turn the power OFF and
ON again.
Replace the Unit if it won't restart.
Check battery and replace if necessary.
Change the PLC Setup setting if battery-
free operation is being used.
Section 11-2
Possible remedy
515