Advertisement

Auxiliary Area
Name
Address
Pulse Output 1 Out-
A28103
put Completed Flag
Pulse Output 1 Out-
A28104
put In-progress Flag
Pulse Output 1 No-
A28105
origin Flag
Pulse Output 1 At-
A28106
origin Flag
Pulse Output 1 Out-
A28107
put Stopped Error
Flag
PWM(891) Output 0
A28300
Output In-progress
Flag
PWM(891) Output 1
A28308
Output In-progress
Flag
420
Description
ON when the number of output pulses set with
the PULS(886)/PLS2(887) instruction has been
output through pulse output 1.
0: Output not completed.
1: Output completed.
ON when pulses are being output from pulse
output 1.
0: Stopped
1: Outputting pulses.
ON when the origin has not been determined for
pulse output 1 and goes OFF when the origin
has been determined.
0: Origin established.
1: Origin not established.
ON when the pulse output PV matches the ori-
gin (0).
0: Not stopped at origin.
1: Stopped at origin.
ON when an error occurred while outputting
pulses in the pulse output 1 origin search func-
tion.
The Pulse Output 1 Output Stop Error code will
be written to A445.
0: No error
1: Stop error occurred.
ON when pulses are being output from
PWM(891) output 0.
0: Stopped
1: Outputting pulses.
ON when pulses are being output from
PWM(891) output 1.
0: Stopped
1: Outputting pulses.
Section 9-11
Read/Write Times when data is
accessed
Read only
• Cleared when
power is turned
ON.
• Cleared when
operation starts or
stops.
• Refreshed at the
start or comple-
tion of pulse out-
put in
independent
mode.
Read only
• Cleared when
power is turned
ON.
• Cleared when
operation starts or
stops.
• Refreshed when
pulse output
starts or stops.
Read only
• Turned ON when
power is turned
ON.
• Turned ON when
operation starts.
• Refreshed when
pulse output
starts or stops.
• Refreshed each
cycle during the
overseeing pro-
cesses.
Read only
• Cleared when
power is turned
ON.
• Refreshed each
cycle during the
overseeing pro-
cesses.
Read only
• Cleared when
power is turned
ON.
• Refreshed when
origin search
starts.
• Refreshed when a
pulse output stop
error occurs.
Read only
• Cleared when
power is turned
ON.
• Cleared when
operation starts or
stops.
Read only
• Refreshed when
pulse output
starts or stops.

Advertisement