PLC Setup
Pulse Output 1 Search Compensation Value 1 (Origin Compensation)
Programming
Settings
Console
address
Word
Bits
+282
00 to 15 80000000 to
7FFFFFFF hex
+283
00 to 15
(See note.)
Pulse Output 1 Origin Search Acceleration Rate
Programming
Settings
Console
address
Word
Bits
+284
00 to 15 Pre-Ver. 2.0 CPU
Units: 0001 to
07D0 hex
CPU Units Ver.
2.0: 0001 to FFFF
hex
(See note.)
Pulse Output 1 Origin Search Deceleration Rate
Programming
Settings
Console
address
Word
Bits
+285
00 to 15 Pre-Ver. 2.0 CPU
Units: 0001 to
07D0 hex
CPU Units Ver.
2.0: 0001 to FFFF
hex
(See note.)
Pulse Output 1 Limit Input Signal Type
Programming
Settings
Console
address
Word
Bits
+286
00 to 03 0 hex: NC
1 hex: NO
328
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Default
---
Sets the pulse output 1 origin com-
pensation (−2,147,483,648 to
2,147,483,647).
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Default
---
Sets the origin search acceleration
rate for pulse output 0.
Pre-Ver. 2.0 CPU Units:
1 to 2,000 pulses/4 ms
CPU Units Ver. 2.0:
1 to 65,535 pulses/4 ms
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Default
---
Sets the origin search deceleration
rate for pulse output 0.
Pre-Ver. 2.0 CPU Units:
1 to 2,000 pulses/4 ms
CPU Units Ver. 2.0:
1 to 65,535 pulses/4 ms
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Default
0 hex
Specifies whether the limit input sig-
nal for pulse output 1 is normally
closed or normally open.
Function
Area flags/
---
Function
Area flags/
---
Function
Area flags/
---
Function
Area flags/
---
Section 7-1
Related
Time when
Auxiliary
setting is read
by CPU Unit
bits
When operation
starts
Related
Time when
Auxiliary
setting is read
by CPU Unit
bits
When operation
starts
Related
Time when
Auxiliary
setting is read
by CPU Unit
bits
When operation
starts
Related
Time when
Auxiliary
setting is read
by CPU Unit
bits
When operation
starts

Advertisement

Table of Contents
loading

Table of Contents