Wiring
Crimp Terminals
Note
!Caution Tighten the AC power supply terminal block screws to the torque of 1.2 N·m.
Note
256
Terminal screws
Recommended wire size
Recommended tightening
torque
Recommended crimp terminals
7 mm max.
Manufacturer
Models
JST Mfg.
V1.25-YS4A
V1.25-M4
V2-YS4A
V2-M4
1. Use crimp terminals for wiring.
2. Do not connect bare stranded wires directly to the terminals.
20 mm max.
Torque to 1.2 N
Loose screws may result in short-circuit, malfunction, or fire.
1. Supply power to all of the Power Supply Units from the same source.
2. Do not remove the protective label from the top of the Unit until wiring has
been completed. This label prevents wire strands and other foreign matter
from entering the Unit during wiring procedures.
3. Do not forget to remove the label from the top of the Power Supply Unit af-
ter wiring the Unit. The label will block air circulation needed for cooling.
M4 self-rising screws
AWG 20 to 14 (0.517 to 2.08 mm
1.2 N·m
7 mm max.
Shape
Y-shaped terminal
with sleeve
Round terminal
with sleeve
Y-shaped terminal
with sleeve
Round terminal
with sleeve
M4 self-raising terminals
m
Section 5-3
2
)
Applicable wire range
(stranded wire)
2
0.25 to 1.65 mm
(AWG
22 to 16)
2
1.04 to 2.63 mm
(AWG
16 to 14)