Omron CJ - 09-2009 Operation Manual page 252

Programmable controllers
Table of Contents

Advertisement

B7A Interface Unit
2) Preparing Cable Signal
Lines
1,2,3...
3) Connecting Cables
204
2. Use vinyl tape or a heat-shrink tube to cover the end of the VCTF cable
sheath, as shown in the following diagram.
Cover with vinyl tape or
heat-shrink tube.
Attach the crimp terminals to the cable's signal lines.
1. Attaching Crimp Terminals
Insert the end of the cable into the terminal and crimp.
Sleeve
Crimp terminal
Signal line
Recommended Crimp Terminals for Cables
Model
AI-series AI0.75-8GY
(Product code: 3200519)
H0.75/14
(Product code: 046290)
TE-0.75
Note Always use the specified crimp tool to attach the crimp terminals. If
a crimp tool is not used, the cable will not be crimped properly, which
may cause the cable to become detached from the terminal.
The following crimp tools are available.
Model
UD6 (Product code: 1204436)
or ZA3 Series
Crimper PZ1.5
(Product code: 900599)
NH77
2. Insulate the stripped end of each signal line with vinyl tape or heat-shrink
tubing.
Use the following procedure to connect cables to the connection terminals.
Orient the connector properly, and then insert the signal lines fully into the
back of each terminal hole in the connector, as shown in the following dia-
gram. (The signal lines are secured in this way, without requiring the use of a
tool.) If crimp terminals are not used on the signal lines, use a small flat-blade
screwdriver to press down on the orange tab to insert the signal lines.
Manufacturer
PHOENIX CONTACT
Nihon Weidmuller Co., Ltd.
NICHIFU Co., Ltd.
Manufacturer
PHOENIX CONTACT
Nihon Weidmuller Co., Ltd.
NICHIFU Co., Ltd.
Section 3-7