Specifications of Basic I/O Units
Terminal Connections
24 V
DC
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate if
polarity is reversed.
• Be sure to wire both terminals 3 and 4 (COM0 (+V)) of CN1.
• Be sure to wire both terminals 1 and 2 ((0 V)) of CN1.
• Be sure to wire both terminals 3 and 4 (COM1) of CN2, and set the same polarity for both pins.
558
Number of Simultaneously ON Points vs.
Ambient Temperature Characteristic
16 points at 33°C
18
16
14
12
10
8
6
4
2
0
0
20
Ambient Temperature
CN1 (Outputs)
I/O word "m"
00
08
L
L
20
19
09
L
01
L
18
17
02
10
L
L
16
15
03
11
L
L
14
13
04
12
L
L
12
11
05
13
L
L
10
9
06
14
L
L
8
7
07
15
L
L
6
5
COM0 (+V)
COM0 (+V)
4
3
0 V
0 V
2
1
16 points at 45°C
Input voltage: 24 V DC
Input voltage: 26.4 V DC
12 points at 55°C
9 points at 55°C
60 (°C)
40
CN2 (Inputs)
I/O word "m+1"
NC
1
COM1
3
15
5
14
7
13
9
12
11
11
13
10
15
24 V
09
DC
17
08
19
Appendix A
NC
2
COM1
4
07
6
06
8
05
10
04
12
03
14
02
16
01
18
00
20