Specifications of Basic I/O Units
Circuit Configuration
When overcurrent is detected, the ERR indicator will light, and the corresponding flag in the Basic I/O Unit
Information Area (A050 to A069) will turn ON.
Terminal Connections
When wiring, pay careful attention to the polarity of the external power supply. The load may operate if the
polarity is reversed.
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
CJ1W-OD232 Transistor Output Unit (MIL Connector, 32 Points, Sourcing)
Output indicator
ERR indicator
Rated Voltage
Operating Load Voltage Range 20.4 to 26.4 V DC
Maximum Load Current
Leakage Current
Residual Voltage
to
24 V DC
24 V DC
0.5 A/point, 2.0 A/common, 4.0 A/Unit
0.1 mA max.
1.5 V max.
Appendix A
581