PLC Setup
Input Operation Setting for IN1
Programming
Settings
Console
address
Word
Bits
+60
04 to 07 0 hex:
Normal (General-
purpose input)
1 hex:
Interrupt (Inter-
rupt input) (See
note.)
2 hex:
Quick (Quick-
response input)
Input Operation Setting for IN2
Programming
Settings
Console
address
Word
Bits
+60
08 to 11 0 hex:
Normal (General-
purpose input)
1 hex:
Interrupt (Inter-
rupt input) (See
note.)
2 hex:
Quick (Quick-
response input)
Input Operation Setting for IN3
Programming
Settings
Console
address
Word
Bits
+60
12 to 15 0 hex:
Normal (General-
purpose input)
1 hex:
Interrupt (Inter-
rupt input) (See
note.)
2 hex:
Quick (Quick-
response input)
320
Default
0 hex
Specifies the kind of input that is
being received at built-in input IN1.
Note When IN1 is set as an interrupt input (1 hex), use the MSKS(690) instruction
to select direct mode or counter mode operation.
Default
0 hex
Specifies the kind of input that is
being received at built-in input IN2.
Note The input operation setting for
Note When IN2 is set as an interrupt input (1 hex), use the MSKS(690) instruction
to select direct mode or counter mode operation.
Default
0 hex
Specifies the kind of input that is
being received at built-in input IN3
Note The input operation setting for
Note When IN3 is set as an interrupt input (1 hex), use the MSKS(690) instruction
to select direct mode or counter mode operation.
Function
Function
IN2 is disabled when high-
speed counter 1 is being used
and the reset method is set to
Phase-Z signal + software
reset.
Function
IN3 is disabled when high-
speed counter 0 is being used
and the reset method is set to
Phase-Z signal + software
reset.
Section 7-1
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When power is
turned ON
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When power is
turned ON
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When power is
turned ON