Explanations of PLC Setup Settings
Startup Mode Setting
PRCN: Programming Console's mode switch
Power ON
Other: PC Setup's Startup Mode setting
Power ON
Note If the backup battery fails or is disconnected, the Forced Status Hold Bit will
be cleared whether this setting is ON or OFF.
OFF (0): Forced Status Hold Bit cleared at start-up
Forced bit status
Mode switch
Retained
Forced Status
Hold Bit: 1 (ON)
ON (1): Forced Status Hold Bit protected at start-up
Forced bit status
Mode switch Retained
Forced Status
Hold Bit: 1 (ON)
This setting determines whether the startup mode will be the mode set on the
Programming Console's mode switch or the mode set here in the PLC Setup.
Note If this setting specifies the mode set on the Programming Console's mode
switch (0) but a Programming Console isn't connected, the CPU Unit will auto-
matically enter RUN mode at startup. (This differs from the default operation
for CS-series CPU Units.)
Mode switch
setting
PRG: PROGRAM mode
MON: MONITOR mode
RUN: RUN mode
Note If a Programming Console is not connected when the PLC Setup is set to use
the mode set on the Programming Console's mode switch, the CPU Unit will
start in RUN mode.
Power
Power
Forced bit status
OFF
ON
Power ON
Not retained
Forced Status
Hold Bit: 0 (OFF)
Power
Power
Forced bit status
OFF
ON
Power ON
Retained
Forced Status
Hold Bit: 1 (ON)
Power ON
Section 7-2
Not retained
when power is
turned ON.
Retained when
power is turned
ON.
RUN mode when
disconnected.
335