7-4-3

2nd Control Function (SET)

Use this function to control two induction motors with different motor parameters by switching.
Even with a single motor, you can use the 2nd control to configure the control and settings that best fit
your application.
To switch between two motors, set the Multi-function Input 1 to 7 Selection (C001 to C007) to 08 (SET)
and turn OFF (1st control) or ON (2nd control) the terminal SET.
Parameter
No.
Multi-function Input 1
C001 to
C007
to 7 Selection
The functions that support motor switching via the terminal SET are as follows.
1st control motor
F002
F003
A001
A002
A003
A004
A020
A041
A042
A043
A044
A045
A046
A047
A061
A062
A081
A082
A092
A093
A094
A095
A096
b012
b013
b021
b022
b023
C041
H002
H003
H004
H005
H006
H020
H021
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Function name
08:
SET (2nd control)
2nd control motor
F001
Output Frequency Setting/Monitor
F202
Acceleration Time 1
F203
Deceleration Time 1
A201
Frequency Reference Selection
A202
RUN Command Selection
A203
Base Frequency
A204
Maximum Frequency
A220
Multi-step Speed Reference 0
A241
Torque Boost Selection
A242
Manual Torque Boost Voltage
A243
Manual Torque Boost Frequency
A244
Control Method
A245
Output Voltage Gain
A246
Automatic Torque Boost Voltage Compensation Gain
A247
Automatic Torque Boost Slip Compensation Gain
A261
Frequency Upper Limit
A262
Frequency Lower Limit
A281
AVR Selection
A282
Motor Rated Voltage Selection
A292
Acceleration Time 2
A293
Deceleration Time 2
A294
2-step Acceleration/Deceleration Selection
A295
2-step Acceleration Frequency
A296
2-step Deceleration Frequency
b212
Electronic Thermal Level
b213
Electronic Thermal Characteristics Selection
b221
Overload Limit Selection
b222
Overload Limit Level
b223
Overload Limit Parameter
C241
Overload Warning Level
H202
Motor Parameter Selection
H203
Motor Capacity
H204
Motor Pole Number
H205
Speed Response
H206
Stabilization Parameter
H220
Motor Parameter R1
H221
Motor Parameter R2