6 Vector Control and Applied Functions
⚫ Recommended product
E6C3-CWZ5GH (Manufacturer: OMRON)
Additional Information
Crosstalk : A phenomenon by which signals are erroneously transmitted between different
Encoder Input
For pulse train input, use the pulse train input EA terminal and the multi-function Input 7 terminal of the
control circuit terminals.
Be sure to use a complementary-output type encoder.
Input signal type
Single-phase pulse train
(P004 = 00)
Phase A and B 90°phase difference
pulse train (P004 = 01)
Single-phase pulse train + direction
(P004 = 03)
*1. Direction signal can be input in favor of the sink or source logic, independent of the output method of the en-
coder signal.
Wiring for Phase A and B 90°Phase Difference Pulse Train (P004 = 01)
Connect the phase-A/B 90° phase difference pulse train as shown in the diagram below.
• Connect the phase-A signal to the pulse train input terminal EA.
• Connect the phase-B signal to the multi-function Input 7 terminal and set the Multi-function Input 7
Selection (C007) to 85 (EB: Rotation direction detection).
• If the encoder signal is connected, you need to complete wiring for other multi-input terminals 1 to 6
in the source logic (PNP).
• The control circuit terminal P24 of the inverter is for a 24-V, 100-mA max. power supply. It can be
used for the encoder power supply if the consumption current for the input terminals in use and the
encoder power supply is allowable. However, this terminal must be isolated from any 24-V system
power supply for other than the encoder and inverter.
6 - 30
phases. Specifically, the rising/falling edge signal from phase A is superimposed on
the signal from phase B and the rising/falling edge signal from phase B is superim-
posed on the signal from phase A, respectively.
Maximum
Frequency
Terminal
EA: 32 kHz
Terminal 7
(Terminal
EB): 32 kHz
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Terminal EA
(5 to 24 VDC, 32 kHz max.)
Single-phase pulse train
Phase-A pulse train
Single-phase pulse train
Terminal 7/EB
(24 VDC, 32 kHz max.)
Phase-B pulse train
*1
Direction signal