Omron MX2 Series User Manual page 177

Multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

Parameter
Function name
No.
b031
Soft Lock Selection
b033
Motor Cable Length
RUN Time/Power ON
b034
Time Detection Level
RUN Direction Limit
b035
Selection
Reduced Voltage
b036
Startup Selection
b037
Display Selection
Initial Screen Selec-
b038
tion
User Parameter
b039
Automatic Setting
Function
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Monitor or data range
00: Data other than b031 cannot be
changed when terminal SFT is ON.
01: Data other than b031 and the set
frequency cannot be changed when
terminal SFT is ON.
02: Data other than b031 cannot be
changed.
03: Data other than b031 and specified
frequency parameter cannot be
changed.
5. to 20.
0: Disabled (Function does not activate)
1. to 65535.
00: No direction limit
01: Only Forward is enabled (Reverse
is limited)
02: Only Reverse is enabled
(Forward is limited)
0: Reduced voltage startup disabled 1
(Reduced voltage startup time: short) to
255 (Reduced voltage startup time:
long)
00: Complete display
01: Individual display of functions
02: User setting + d001, F001, b037
03: Data comparison display
05: Monitor display + b037
000: Screen on which the Enter key
was last pressed
001 to 060: d001 to d060
201: F001
202: Do not set.
00: Disabled
01: Enabled
4 Parameter List
Changes
Default
Set
during
data
data
RUN
01
Enabled
10.
Enabled
0.
Enabled
00
Disabled
2
Enabled
Enabled
00
001
Enabled
00
Enabled
Unit
Page
P. 7-54
m
P. 6-4
10 h
P. 7-84
P. 7-38
4
P. 7-36
P. 5-3
P. 7-56
P. 7-60
4 - 17