Capacitor Life Warning Signal (Wac); Cooling Fan Operation - Omron MX2 Series User Manual

Multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

Parameter
No.
C142
Logic Output Signal 1 to 3
C145
Selection 1
C148
C143
Logic Output Signal 1 to 3
C146
Selection 2
C149
C144
Logic Output Signal 1 to 3
C147
Operator Selection
C150
Multi-function Output 11/12
Selection, Multi-function Relay
C021, C022,
C026
Output (AL1, AL2) Function
Selection

7-8-12 Capacitor Life Warning Signal (WAC)

Use this signal to determines the life expectancy of the capacitor on the option board based on the
inverter's internal temperature and conduction time.
The status of this signal can be monitored in the Life Assessment Monitor (d022).
Set this function according to A-2 Smoothing Capacitor Life Curve on page A-7.
Parameter
No.
Multi-function Output 11/12
C021, C022
Selection
Multi-function Relay Output
C026
(AL1, AL2) Function Selection

7-8-13 Cooling Fan Operation

Select whether to enable the inverter's built-in cooling fan constantly or only during inverter operation.
Parameter
No.
b092

Cooling Fan Operation

b093
Total Fan Operation Time Clear
Note 1. If a momentary power interruption or power shutoff occurs when the cooling fan is operating, the cooling
fan will stop temporarily and, after power recovery, restart automatically.
2. Clear the total operation time only when you replace the cooling fan. Otherwise, the Life Assessment
Monitor (d022) will not display correct monitor data.
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Function name
00 to 63: Same as options for C021
(Except 33 (LOG1) to 35 (LOG3), 63
(OPO), and 255 (no))
00:
01:
02:
33:
34:
35:
Function name
39:
Function name
00:
01:
02:
00:
01:
Data
AND
OR
XOR
LOG1: Logic operation output 1
LOG2: Logic operation output 2
LOG3: Logic operation output 3
Data
WAC
(Capacitor life warning signal)
Data
Always
Enabled only during operation
(Note that the cooling fan is
also enabled for 3 min after
power-on and 3 min after
inverter operation stop.)
Dependent on cooling fin tem-
perature (Enabled above
approximately 40°C)
Clear disabled (Value increas-
ing continuously)
Clear with the Enter key
(Data is reset from 01 to 00
after execution.)
7 Other Functions
Default
Unit
data
00
00
00
Default
Unit
data
Default
Unit
data
01
00
7 - 87