⚫ PM Motor Parameter R (H106)
Set the wiring resistance (in
Alternatively, set 50% of the measured phase-to-phase resistance of the motor.
⚫ PM Motor Parameter Ld (H107)
Set the d-axis inductance (in mH) of the motor in Y-connection.
Alternatively, set 50% of the phase-to-phase inductance of the motor measured with an LCR meter.
Be sure to set this parameter so that Ld is equal to or less than Lq. Not doing so may result in an
overload.
⚫ PM Motor Parameter Lq (H108)
Set the q-axis inductance (in mH) of the motor in Y-connection.
Alternatively, set 50% of the phase-to-phase inductance of the motor measured with an LCR meter.
Be sure to set this parameter so that Ld is equal to or less than Lq.
⚫ PM Motor Parameter Ke (H109)
Set the inductive voltage parameter of your PM motor in Vp/(rad/s).
This value must be set in "Vp/(rad/s)." If the datasheet provides this parameter in a different unit, you
need to perform unit conversion.
Example
If the inductive voltage parameter for one phase is 10 [mV/r/min], the set value can be calculated as
follows:
10 [mV/r/min] = (10/1000 [V])
⚫ PM Motor Parameter J (H110)
Calculate the motor-shaft conversion of the moment of load inertia, add the moment of inertia of the
motor to it, and set the sum.
⚫ Motor Cable Length (b033)
Set the cable length from the inverter to the motor.
To maximize the performance of the inverter, set the cable length to 20 m or shorter.
Parameter
No.
A003
1st Base Frequency
A004
1st Maximum Frequency
b033
Motor Cable Length
1st Motor Rated Voltage
A082
Selection
PM Motor Parameter
H102
Selection
H103
PM Motor Capacity
H104
PM Motor Pole Number
H105
PM Motor Rated Current
1st Electronic Thermal
b012
Level
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
) on the primary side of the motor for one phase in Y-connection.
(√2)
(60 [s]) / ((2
Function name
30.0 to 1st Maximum Frequency (A004)
1st Base Frequency (A003) to 400.0
5. to 20.
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
00:
02:
0.1/0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/4.0/
5.5/7.5/11.0/15.0/18.5
2/4/6/8
10 to 48: Do not set.
0.20  Rated current to 1.00  Rated current
0.20  Rated current to 1.00  Rated current
6 Vector Control and Applied Functions
4 [pole] / 2) [rad]) = 0.0675 [Vp/(rad/s)]
Data
Standard PM motor parameter
Auto-tuning parameter
6
Default
Unit
data
60.0
Hz
60.0
Hz
10.
m
200 or 400
V
00
Maximum
applicable
kW
motor
capacity
Dependent
pole
on capacity
Rated cur-
A
rent
Rated cur-
A
rent
6 - 63