Advertisement

Parameter
Function name
No.
Communication
Speed Selection
C071
(Baud Rate Selec-
tion)
Communication Sta-
C072
tion No. Selection
Communication Par-
C074
ity Selection
Communication Stop
C075
Bit Selection
Operation Selection
C076
on Communication
Error
Communication Error
C077
Timeout Time
Communication Wait
C078
Time
C081
O Adjustment
C082
OI Adjustment
Thermistor Adjust-
C085
ment
C091
(Reserved)
Communication
C096
Selection
Co-inverter Commu-
C098
nication Starting Sta-
tion Number
Co-inverter Commu-
C099
nication Ending Sta-
tion Number
Co-inverter Commu-
C100
nication Start Selec-
tion
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Monitor or data range
03: 2400 bps
04: 4800 bps
05: 9600 bps
06: 19.2 kbps
07: 38.4 kbps
08: 57.6 kbps
09: 76.8 kbps
10: 115.2 kbps
1. to 247.
00: No parity
01: Even parity
02: Odd parity
1:
1 bit
2:
2 bits
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free-run stop
04: Deceleration stop
0.00: Timeout disabled
0.01 to 99.99
0. to 1000.
0.0 to 200.0
0.0 to 200.0
0.0 to 200.0
Do not change the default 00.
00: Modbus communication
01: Co-inverter communication
02: Co-inverter communication (man-
agement inverter)
1. to 8.
1. to 8.
00: Start via 485 terminal
01: Constant communication
4 Parameter List
Changes
Default
Set
during
data
data
RUN
05
Enabled
1.
Enabled
00
Enabled
1
Enabled
02
Enabled
0.00
Enabled
0.
Enabled
100.0
Enabled
100.0
Enabled
100.0
Enabled
00
00
Enabled
1.
Disabled
1.
Disabled
00
Disabled
Unit
Page
P. 8-5
P. 8-5
4
s
ms
%
P. 7-25
%
%
P. 7-82
P. 8-31
4 - 29