Factory Default Setting - Toshiba TOSVERT VF-P7 Instruction Manual

Inverter for fan and pump applications
Hide thumbs Also See for TOSVERT VF-P7:
Table of Contents

Advertisement

5.5 Factory default setting

 :Standard setting mode selection
・ Function
This parameter is to set two or more parameters at a time for different commands.
Using this parameter, all parameters can be also return to their respective default settings by
one operation, and save or set specific parameters individually.
Title
Standard setting

mode selection
★This parameter is used to change the settings of other parameters. Therefore, 0 is always displayed.
★This parameter cannot be used when the inverter is in operation. So, put the inverter out of operation
before using this parameter.
★You can check the previous settings by selecting  last set data in status monitor mode. (Refer to 8.1
for details.)
[Set value]
[ 50 Hz standard setting (  = ) ]
Setting at  causes all the following parameters to be set for operation using a
base frequency of 50Hz.(This does not change the settings of any other parameters.)
・ Maximum frequency : 50Hz
・ Base frequency #1 : 50Hz
・ Base frequency #2 : 50Hz
・ Base frequency #3 : 50Hz
・ Base frequency #4 : 50Hz
・ Upper limit frequency : 50Hz
・ Forward speed limit input level : 50Hz ・ Point #2 frequency : 50Hz
・ Reverse speed limit input level : 50Hz
・ Automatic light-load high-speed operation frequency : 50Hz
・ Commercial power/inverter switching frequency : 50Hz
[ 60 Hz standard setting (  = ) ]
Setting  at  causes all the following parameters to be set for operation using a
base frequency of 60Hz.(This does not change the settings of any other parameters.)
・ Maximum frequency : 60Hz
・ Base frequency #1 : 60Hz
・ Base frequency #2 : 60Hz
・ Base frequency #3 : 60Hz
・ Base frequency #4 : 60Hz
・ Upper limit frequency : 60Hz
・ Forward speed limit input level : 60Hz ・ Point #2 frequency : 60Hz
・ Reverse speed limit input level : 60Hz
・ Automatic light-load high-speed operation frequency : 60Hz
・ Commercial power/inverter switching frequency : 60Hz
Function
: -
: 50Hz standard setting
: 60Hz standard setting
: Factory default setting
: Trip clear
: Clearing accumulating operation time
: Initialization of type form information
: Memorization of user-defined parameters
: Reset of user-defined parameters
E-13
Adjustment range
・ VI/II reference point #2 frequency : 50Hz
・ RR reference point #2 frequency : 50Hz
・ RX reference point #2 frequency : 50Hz
・ RX2 reference point #2 frequency : 50Hz
・ BIN reference point #2 frequency : 50Hz
・ Pulse reference point #2 frequency : 50Hz
・ VI/II reference point #2 frequency : 60Hz
・ RR reference point #2 frequency : 60Hz
・ RX reference point #2 frequency : 60Hz
・ RX2 reference point #2 frequency : 60Hz
・ BIN reference point #2 frequency : 60Hz
・ Pulse reference point #2 frequency : 60Hz
Default setting