[ Factory default setting (  =  ) ]
Setting  at  returns all parameters to their respective default settings.
When this parameter is set at 3,
is displayed for a while, then switches back

to the original display (
or
 ). Note that this setting also clears all trouble

history records.
[ Trip clear (  =  ) ]
Setting  at  clears the oldest 4 trip history records.
(This setting does not change any parameter settings.)
[ Clearing accumulating operation time (  =  ) ]
Setting  at  clears the cumulative operation time (resets it to zero).
[ Initialization of type form information (  =  ) ]
When a trip occurs because of a type error ( is displayed), you can clear the
trip by setting  at . This function is used to reformat a control circuit board to
adapt it to an inverter, for example, when a circuit board is removed from an inverter to
      use for another inverter for maintenance or for other reasons. This setting clears all
type data stored in the inverter.
[ Memorization of user-defined parameters ( =  ) ]
Setting  at  causes all the current parameter settings to be stored individually.
[ Reset of user-defined parameters (  =  ) ]
Setting  at  returns all parameters to the settings saved by setting this
parameter at .
The above settings  and  allows you to have your own default parameter settings.
E-14