4.
Press the Run key (green Run LED illuminates red) and the motor runs at the Frequency
Command value.
Note:
The speed of the motor may be changed while the motor is running by using the
Rotary Encoder to change the Frequency Command value.
5.
Press the Stop-Reset key to stop the motor.

Default Setting Changes

To change a default parameter setting, go to the root of the Program menu and turn the Rotary
Encoder until the desired parameter group is within the cursor block. Press the Rotary Encoder (repeat
if there is a submenu).
Press the Rotary Encoder to select the default setting to be changed. The selection takes on the reverse
video format (dark background, light text). Turn the Rotary Encoder to change the value of the
parameter. To exit the menu without saving the change, press the ESC key. To save the new setting,
press the Rotary Encoder.
Note:
Some parameters (e.g., F800, F801, F805, etc.) require that the ASD be Reset or
powered off and then on again in order to enable the new setting.
For a complete listing of the Program menu items, see the section titled
Navigation on pg.
listed where applicable. From any menu, press the Mode key to return to the root menu. Repeated
Mode key entries loop the system through the root menus as shown in
The default settings may also be changed by entering the Parameter Number of the setting to be
changed at the Direct Access menu (Program Direct Access applicable parameter number). A
listing of the Direct Access/Parameter Numbers and a description of the associated parameter may be
found in the section titled
Search For Default Setting Changes
A listing of all parameters that have been changed from the factory default settings may be viewed
sequentially by accessing the Changed From Default screen (Program Utilities Changed
From Default).
The Changed From Default feature allows the user to view (and/or change) the parameters that are
different from the factory default or post-reset settings. Once the Changed From Default screen is
displayed, the system automatically scrolls through all of the system parameters and halts once reaching
a changed parameter.
The Rotary Encoder may be clicked once clockwise to continue scrolling forward or clicked once
counterclockwise to begin scrolling in reverse. With each click of the Rotary Encoder from a stop, the
system scrolls and stops at the next parameter that has been changed.
Pressing the Rotary Encoder while a changed parameter is displayed accesses the settings of the
changed parameter for viewing or changing.
Pressing ESC while the system is performing a Changed From Default search terminates the search.
Pressing ESC when done searching (or halted at a changed parameter) returns the system to the
Program Menu.
Pressing the Mode key when finished searching or when halted at a changed parameter returns the
system to the primary menu loop.
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
46. The menu items are mapped for convenience, and Direct Access Numbers are
Direct Access Parameter Information on pg.
Program Mode Menu
Figure 28 on pg.
41.
82.
35

Advertisement

Table of Contents
loading

Table of Contents