     ■Output terminal function(open collector, relay outputs) settings and detection levels
Technical terms
Alarm:・・・・・・・・・・・・・・ Alarm output beyond a certain setting value
Pre-alarm: ・・・・・・・・・・ Alarm output of the state where the inverter may carry out a trip by
Serious failure: ・・・・・・ Output signal in a serious failure of the protection function of the inverter.
Light failure: ・・・・・・・・ Output signal in a slight failure of the protection function of the inverter.
Emergency stop: ・・・・ Output signal when the inverter comes into emergency stop.
Table of output terminal functions and detection levels
Parameter setting
Positive
Negative
logic
logic
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
continuation
(Arm over-current(, , ), Load side over-current(), Short-
circuiting(, ), Phase failure(, ), etc.)
(Over-load(, ), Over-voltage(, , ), Over-current(,
, , , , ), etc.)
Stopping manner is set with (emergency stop).
Function
Lower limit frequency
()
Upper limit frequency
()
Low speed signal
Acceleration/deceleration
completion
Specified speed arrival
Failure FL (all trip)
Failure FL (except for
 and )
Over-current pre-alarm
Inverter overload
pre-alarm
Motor overload
pre-alarm
Overheat pre-alarm
Over-voltage pre-alarm
Main circuit
under-voltage ()
detected
Low current detected
Over-torque detected
Braking resistor overload
() pre-alarm
In emergency stop
In course of retry
Pattern run switching
output
Operation output specifications (in case of positive logic)
"ON": The running frequency is equal to or higher than the setting
of (Lower limit frequency).
"OFF": The running frequency is lower than the setting of .
"ON": The running frequency is equal to or higher than the setting
of (Upper limit frequency).
"OFF": The running frequency is lower than the setting of .
"ON": The running frequency is equal to or higher than the setting
of (low-speed signal output frequency).
"OFF": The running frequency is lower than the setting of .
"ON": The difference between the frequency command and the
running frequency is within the setting of .
"OFF": In acceleration or deceleration.
"ON": The running frequency is in the range of ±.
"OFF": The running frequency is out of the range of
±.
"ON": Inverter is tripped.
"OFF": Inverter trip is cancelled.
"ON": Inverter is tripped (except EF and OCL).
"OFF": Inverter trip is cancelled (reset).
"ON": Inverter output current is over the (Stall prevention
level) set value.
"OFF": Inverter output current is under the  set value.
"ON": A certain rate of inverter overload() detection time is over.
"OFF": The detection time is within a certain limit.
"ON": A certain rate of motor overload() detection time is over.
"OFF": The detection time is within a certain limit.
"ON": The temperature of the cooling fin is 85℃ or higher inside
the inverter.
"OFF": The temperature drops to 80℃ or lower after overheat
pre-alarm was on.
"ON": In over-voltage control operation or PB operation.
(200V class: 370 VDC approx., 400V class: 740 VDC approx.)
"ON": The main circuit voltage is lower than the main circuit under-
voltage detection () level.
(200V class: 200 VDC approx., 400V class: 380 VDC approx.)
"ON":  is set at  and the state that inverter output current is
 set value or larger continued more than  set
value.
"ON": The state that torque current component is ()
set value or larger continued more than  set value.
"ON": A certain rate of braking resister overload trip()
detection time is over.
"OFF": The detection time is within a certain limit.
"ON": In emergency stop operation ("" is indicated).
"OFF": No emergency stop operation is performed.
"ON": In retry operation ("" is indicated).
"OFF": No retry operation is performed.
"ON": In normal operation or pattern operation has finished.
"OFF": In pattern operation.