System Operation

W7B ASD Installation & Operation Manual
System Operation

Startup Wizard

The Startup Wizard launches upon the first power
up of the system and assists with the initial
configuration of the input power settings and the
output parameters of the W7B ASD. The W7B ASD
may also be setup via communications, by directly
accessing the individual parameters via the menu
hierarchy, or using the Direct Access parameter
numbers (see
pg.
51).
See the section titled

Default Setting Changes

more information on changing the parameter
settings.
After the initial execution of the Startup Wizard at
the first power up, the wizard may only be run by
setting the following menu item to Yes — Program
 Utilities  Display Parameters  Display the
startup wizard next power-up?
Upon the next power up, the system will launch to
the Startup Wizard. Once completed, the system
will set the Display the startup wizard next power-
up? setting to No (for the next system power up)
and normal startups will resume.
The Startup Wizard querys the user for the
following information:
1.
The
Voltage and Frequency Rating of the
Motor.
2. The
Upper Limit
Frequency.
3. The
Lower Limit
Frequency.
4.
Adjust Accel/Decel Automatically
Enabled, continue from step #7).
5. The
Acceleration
Time.
6. The
Deceleration
Time.
7.
The
Volts Per Hertz
8. The
Motor Current
9. The
Motor
Capacity.
10. The
Command
Source.
11. The
Frequency Command
12. The
Display Units
Click Exit to load the settings of the Startup Wizard
into the ASD.
See the section titled
Startup Wizard Requirements
on pg. 47
for additional information on the Startup
Wizard.
30
for
(if
Setting.
Rating.
Source.
for current and voltage.

Operation (Hand)

To run the motor, perform the following steps:
1. Press the MON/PROG key until the
Frequency Command screen is displayed (see
Figure 24 on pg.
32).
2. Place the system in the Hand mode by
pressing the Hand/Auto key.
3. Ensure that there are no personnel near
the motor or the motor-driven equipment.
4. Using the Rotary Encoder, dial in a speed
setting at the Set field and press the Rotary
Encoder.
5. Press the Run key (illuminated green RUN
LED turns red) and the motor will accelerate to
the set speed at the (default) programmed rate.
The speed may be changed while running.
6. Press the Stop-Reset key to stop the motor.
Default Setting Changes
To change a parameter setting using the EOI, press
the MON/PRG key until the Program menu is
displayed.
From the Program menu, scroll to the desired
parameter group and press the Rotary Encoder.
Repeat for sub-menu items. Once reaching the
lowest level of a parameter group, scroll to the
parameter to be changed and press the Rotary
Encoder.
The parameter takes on the reverse video format
(dark background/light text). Use the Rotary
Encoder to scroll to the new value or setting. Press
the ESC key to exit without saving the parameter
change while still in the reverse video mode or
press the Rotary Encoder to accept and save the
change.
For a complete listing of the Program menu items,
see the section titled
Program Menu Navigation on
pg.
35. The Direct Access Numbers are listed
where applicable. The Direct Access Numbers are
also listed in the section titled
Parameter Information on pg.
The default settings may also be changed by
entering the Parameter Number of the setting to be
changed at the Direct Access menu (Program 
Direct Access Applicable Parameter Number). A
listing of all parameters that have been changed
from the default setting may be viewed sequentially
https://www.toshiba.com/tic/
Direct Access
51.