Standard Default Setting; Factory Default Setting - Toshiba TOSVERT VF-AS1 Instruction Manual

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

5.20

Standard default setting


• Function
This parameter is to set two or more parameters at a time for different commands. Using this parameter, all
parameters can be also return to their respective default settings by one operation, and save or set specific
parameters individually.
Title

5
Note 1: This parameter is used to change the settings of other parameters. Therefore,  is always displayed.
Note 2:  cannot be set during the inverter operating. Always stop the inverter first and then program.
Note 3: When parameter  is invoked, the value set previously is displayed on the left side of the parameter.
Note 4: If  is set to , the optional communication devices DEV002Z, PDP002Z and CCL001Z cannot be
used with the inverter. (The personal computer communications software PCM001Z cannot be used, either.)
Furthermore, the copy function of the LED extended panel option (RKP002Z) does not work normally, so use
only the parameter setting function and the monitoring function.
Note 5: If the power is turned off while the parameter  is being set, an error () will occur when the power
is turned back on. If the error occurs, set  again.
[Programmed value]
50Hz default setting (=)
Setting  at  causes all the following parameters to be set for operation using a base frequency of 50Hz.
(This does not change the settings of any other parameters.)
• Maximum frequency 
• Base frequency 1 
• Base frequency 2 
• Base frequency 3 
• Base frequency 4 
• Upper limit frequency 
• Forward speed limit input level 
• Reverse speed limit input level 
• Commercial power/inverter switching frequency  : 50Hz
• Point 2 frequency 
• Automatic light-load high-speed operation frequency  : 50Hz

: Factory default setting

Function
: –
:50Hz default setting
:60Hz default setting
:Factory default setting
:Trip clear
:Cumulative operation time cleared
:Initialization of type information
Factory default
:Save user-defined parameters
setting
:Reset of user-defined parameters
:Cumulative fan operation time record clear
:Acceleration/deceleration time setting 0.01 sec.~600.0 sec.
[Note 4]
:Acceleration/deceleration time setting 0.1 sec.~6000 sec.
:500V-50Hz default setting
:575V-60Hz default setting
:690V-50Hz default setting
Adjustment range
: 50Hz
• VI/II input point 2 frequency 
: 50Hz
• RR/S4 input point 2 frequency 
: 50Hz
• RX input point 2 frequency 
: 50Hz
• AI1 input point 2 frequency 
: 50Hz
• AI2 input point 2 frequency 
: 50Hz
• RP/high-speed pulse input point 2 frequency 
: 50Hz
• PID deviation upper limit 
: 50Hz
• PID deviation lower limit 
• Process upper limit 
: 50Hz
• PID output upper limit 
• Motor rated rotational speed :1400~1480min-1 (According to model)
E-42
E6581528
Default setting
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz