6.2.3 Assigning priority to the terminal board in panel operation mode


・Function
This parameter is used to give priority to certain external commands entered from the
terminal board in control panel operation mode, for example, when jogging the motor by
giving signals externally.
■Parameter setting
Title

[: Disabled (Terminal board has no priority)]
Priority is given always to commands (operation commands) entered from the control
panel. To give priority to commands from the terminal board, it is necessary to switch
from control panel operation to terminal board operation by sending signals through the
terminal board.
Command from the control panel
(=)
Command from the terminal board
The motor runs in reverse direction if F-CC and R-CC
are closed simultaneously.
The motor slows down to a stop if F-CC and R-CC are
closed simultaneously.
:Priority setting of input terminal
Function
Priority setting of input terminal
Adjustment range
: Disabled,: Enabled
The mode switching terminals are
used to switch to terminal board o
peration mode. (Refer to G-4)
F-4
Forward
[s]
Reverse
ON
OFF
ON
OFF
Forward
[s]
Reverse
ON
OFF
ON
OFF
Default setting
Internal command