Toshiba TOSVERT VF-P7 Instruction Manual page 174

Inverter for fan and pump applications
Hide thumbs Also See for TOSVERT VF-P7:
Table of Contents

Advertisement

Parameter setting
Positive
Negative
Function
logic
logic
38
39
PID deviation limit
40
41
Run/stop
42
43
Serious failure
44
45
Light failure
Commercial/INV
switching output #1
46
47
(for inverter operation
output)
Commercial/INV
switching output #2
48
49
(for commercial
operation output)
50
51
Cooling fan ON/OFF
52
53
In Jog run
Panel operation/terminal
54
55
board operation
switching
Cumulative operation
56
57
time alarm
Abnormal communication
58
59
alarm #1
(caused by scanning)
Forward/reverse
60
61
switching
62
63
Ready for operation #1
64
65
Ready for operation #2
Poor control power supply
66
67
() pre-alarm
System consistent
68
69
sequence
(BR: Brake release)
70
71
In (pre-)alarm status
Forward speed limit
72
73
(torque control)
Reverse speed limit
74
75
(torque control)
76
77
Inverter healthy output
Abnormal communication
alarm #2 (caused by
78
79
RS485 logic or
message transmission)
80
81
Error code output #1
82
83
Error code output #2
84
85
Error code output #3
86
87
Error code output #4
88
89
Error code output #5
90
91
Error code output #6
Operation output specifications (in case of positive logic)
"ON": PID deviation is in  or  set value.
"ON": Running frequency is output or DC injection breaking ()
is performed.
"ON": Serious failure(, , , phase failure, abnormal
output, short-circuit) is detected.
"OFF": Inverter has recovered from serious failure. (Serious failure
has been reset)
"ON": Light failure (, , , , ) is detected.
"OFF": Inverter has recovered from light failure. (Light failure has
been reset)
Refer to 6.16.
Refer to 6.16.
"ON": Cooling fan is in operation.
"OFF": Cooling fan is off operation.
"ON": In jog run.
"OFF": In normal operation.
"ON": In operation by terminal board.
"OFF": In operation by control panel.
"ON": Cumulative operation time is beyond the  set value.
"OFF": Cumulative operation time is less than the  set value.
"ON": Communication error caused by scanning has occurred.
"OFF": Communication error is cancelled (reset).
"OFF": In forward operation.
"ON": In reverse operation.
(The last status is held while operation is suspended.)
"ON": In operable status or operation can be started with frequency
command input as an operation switching answer-back.
"OFF": In inoperable status.
"ON": In operable status or operation can be started with ST and
RUN signals and frequency command input
"OFF": In inoperable status.
"ON": Control circuit under-voltage is detected ().
(detection level; 200V class: approx. 145 VAC or lower,
400V class: approx. 290 VAC or lower)
Output the braking signal according to the brake sequence.
"ON": More than one of alarm, pre-alarm, under-voltage, low
current over-torque, poor control power supply, PID deviation
limit, abnormal frequency setting or torque limit have occurred
or detected.
"OFF": All the alarms above are cancelled.
"ON": Forward operation speed is  set value or over.
"OFF": Forward operation speed is less than  set value.
"ON": Reverse operation speed is  set value or over.
"OFF": Reverse operation speed is less than  set value.
"ON" and "OFF" are alternately output at intervals of 1 second.
"ON": Communication error caused by RS485 logic or message
transmission has occurred.
"OFF": Communication error is cancelled (reset).
Output the failure code in 6bits.
G-7