6.25.12 Over-voltage stall protection level
:Over-voltage stall protection level(high response)
:Over-voltage stall protection level
*Refer to 6.13.5 for details.
6.25.13 Under-voltage trip
:Under-voltage trip mode
:Under-voltage detection time
・Function
This parameter is to select the action when detecting an under-voltage. (Invalid, while the
inverter stops.) If is set at (Enabled), it is necessary to set, with , the time
elapsed before the inverter trips after the detection of an under-voltage.
=
=
Title
Under-voltage trip mode
Under-voltage detection time
6.25.14 UV stall level
:Under-voltage stall level
・Function
This parameter is used to set the operation level of the regenerative power
ride-through control and the deceleration stop. (Refer to 6.13.2)
Title
Under-voltage stall level
6.25.15 System-supporting sequence (B-timer)
:System-supporting sequence (B-timer)
・Function
This parameter is used to set the waiting time for answer from system(Input terminal function
setting: System-supporting sequence (BA:,) ). After start of operation, if no answer
is received in set time(), the inverter trips().
Title
System-supporting sequence (B-timer)
:Disabled・・・・Inverter stops, but does not trip.(FL is not active)
:Enabled・・・・The inverter trips if an under-voltage passes for the time
set with
Function
Function
Function
or over. (FL is active)
Adjustment range
: Disabled, : Enabled
∼ [s]
Adjustment range
∼ [%]
Adjustment range
: Invalid
∼ [s]
F-60
Default setting
Default setting
Default setting