Control Mode Selection - Toshiba TOSVERT VF-P7 Instruction Manual

Inverter for fan and pump applications
Hide thumbs Also See for TOSVERT VF-P7:
Table of Contents

Advertisement

      

5.10 Control mode selection

 :Motor control mode selection
・ Function
The VF-P7 has the following V/f control modes:
・ Constant torque characteristic
・ Variable torque mode
・ Automatic torque boost *1
・ Sensorless vector control (speed) *1
・ Automatic torque boost + automatic energy-saving
・ Sensorless vector control + automatic energy-saving *1
・ V/f 5-point setting
・ Sensorless vector control (torque/speed switching)
・ PG feedback vector control (torque/speed switching)
・ PG feedback vector control (torque/position switching)
(*1) The automatic control parameter automatically sets this parameter and the
auto-tuning parameter at a time.
■Parameter setting
Title
Motor control

mode selection
1) Constant torque characteristic (Normal way of use)
[Set the motor control mode selection  at (Constant torque characteristic)]
Usually, this control mode is used for loads, such as belt conveyers and cranes, that
require the same torque as that produced at the rated speed, even at low speeds.
Base-frequency voltage #1
Output voltage [V]
                        => Refer to 5.1.2 for details.
Function
: Constant torque characteristic
: Square reduction torque characteristic
: Automatic torque boost
: Sensorless vector control
: Automatic torque boost + automatic energy-saving
: Sensorless vector control (speed) + automatic energy-saving
: V-f 5-points setting
: Sensorless vector control (torque/speed switching)
: PG feedback vector control (speed/torque switching)
: PG feedback vector control (speed/position switching)


0
To further increase the torque, use the manual torque boost parameter .
Adjustment range
(speed)
Base frequency #1 
E-17
Default setting
Output frequency [Hz]