6. Extended parameters

Extended parameters are used for sophisticated operation, fine adjustment and special purposes.
Change parameter settings, as required.
Extended parameter list => Refer to Chapter 10.
6.1 Frequency signals

6.1.1 Low-speed signal


・Function
When the output frequency exceeds the frequency set with the parameter F100, an ON
signal is put out. The function of this parameter is to send a signal for exciting or releasing
an electromagnetic brake.
★through the open collector terminal OUT1 or OUT2 (24 Vdc - max. 50 mA). (Default setting: OUT 1)
[Parameter setting]
Tytle

Low-speed signal output (Default setting)
(
Low-speed signal output: Inversion
[Connection diagram (Sink logic)]
Output terminal setting
The low-speed signal (ON signal) output function has been assigned to the
terminal OUT1 by default. To invert output signals, it is necessary to change
the setting of the output terminal selection parameter.
[Parameter setting]
Title

Note) To use OUT2 terminal, set the parameter .
:Low-speed signal output frequency
Function
Low-speed signal output frequency
Output frequency [Hz]
Set frequency

0
P24-OUT1
P24-OUT1
Ry
Function
Output terminal
selection #1 (OUT1)
Speed control mode Torque control mode
Adjustment range
∼
P24
OUT1(or OUT2)
Adjustment range
: Low speed signal(a-contact)
∼
: Low speed signal(b-contact)
F-1
Default setting

[s]
ON
OFF
)
ON
OFF
Set value
or