Dc Injection Braking - Toshiba TOSVERT VF-P7 Instruction Manual

Inverter for fan and pump applications
Hide thumbs Also See for TOSVERT VF-P7:
Table of Contents

Advertisement

[Parameter setting]
Title

Frequency after 0Hz
dead band operation
carried out.

0 [Hz]

6.8 DC injection braking

6.8.1 DC injection braking
 :DC injection braking start frequency
 :DC injection braking current
 :DC injection braking time
 :Forward/reverse DC braking priority control
・Function
These parameters apply a direct current to the motor to obtain large braking torque.
These parameters are used to set the direct current to be applied to the motor, the
braking time and the braking start frequency.
[Parameter setting]
Title




Output frequency [Hz]
DC injection braking
start frequency
Output current [A]
Operating signal(F-CC)
Note) The sensitivity of the inverter's overload protective function increases during D.C. braking. To avoid
tripping, the inverter may automatically adjust the D.C. braking rate.
<D.C. braking start conditions>
The forward/reverse DC braking priority control function  recognizes certain conditions as
stop commands from the inverter, and is activated when the output frequency goes down below
the DC injection braking start frequency set with . In this case, the conditions under which
DC injection braking starts include not only the issue of a start or stop command from the control
panel or an external input device, but also a fall in the reference frequency below the value set with
 (stop frequency setting) or a fall in the output frequency below the operation stop
frequency.
Function
0Hz dead band frequency
notes 1) This function is invalid to preset-speed operation.
notes 2) It is effective as frequency instructions to the
notes 3) The addition and multiplication of the override
Frequency reference
Function
DC injection braking start frequency
DC injection braking current
DC injection braking time
Forward/reverse DC braking priority control
Reference

Adjustment range
∼ [Hz]
frequency reference chosen by the priority
processing by , , communication, etc.
function is carried out to the frequency in which
this function operated.
Adjustment range
∼ [Hz]
∼ [%]
∼ [s]
: OFF, : ON
DC injection braking
Display of  blinks
[s]
DC injection braking time
ON
OFF
F-15
Default setting

Default setting




DC injection braking current



Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents