Standard Default Setting - Toshiba TOSVERT VF-AS1 Instruction Manual

The new generation high-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

5.20

Standard default setting


• Function
This parameter is to set two or more parameters at a time for different commands. Using this parameter, all
parameters can be also return to their respective default settings by one operation, and save or set specific
parameters individually.
[Parameter setting]
Title

5
This parameter is used to change the settings of other parameters. Therefore,  is always displayed.
 cannot be set during the inverter operating. Always stop the inverter first and then program.
When parameter  is invoked, the value set previously is displayed on the left side of the parameter.
[Programmed value]
50Hz default setting (=)
Setting  at  causes all the following parameters to be set for operation using a base frequency of 50Hz.
(This does not change the settings of any other parameters.)
• Maximum frequency 
• Base frequency 1 
• Base frequency 2 
• Base frequency 3 
• Base frequency 4 
• Upper limit frequency 
• Forward speed limit input level 
• Reverse speed limit input level 
• Commercial power/inverter switching frequency  : 50Hz
• Point 2 frequency 
• Automatic light-load high-speed operation frequency  : 50Hz
60Hz default setting (=)
Setting  at  causes all the following parameters to be set for operation using a base frequency of 60Hz.
(This does not change the settings of any other parameters.)
• Maximum frequency 
• Base frequency 1 
• Base frequency 2 
• Base frequency 3 
• Base frequency 4 
• Upper limit frequency 
• Forward speed limit input level 
• Reverse speed limit input level 
• Commercial power/inverter switching frequency  : 60Hz
• Point 2 frequency 
• Automatic light-load high-speed operation frequency  : 60Hz
: Default setting
Function
Factory default setting
Adjustment range
: –
:50Hz default setting
:60Hz default setting
:Factory default setting
:Trip clear
:Cumulative operation time cleared
:Initialization of type information
:Save user-defined parameters
:Reset of user-defined parameters
:Cumulative fan operation time record clear
:Acceleration/deceleration time setting
0.01 sec.~600.0 sec.
:Acceleration/deceleration time setting 0.1
sec.~6000 sec.
: 50Hz
• VI/II input point 2 frequency 
: 50Hz
• RR/S4 input point 2 frequency 
: 50Hz
• RX input point 2 frequency 
: 50Hz
• A1 input point 2 frequency 
: 50Hz
• A2 input point 2 frequency 
: 50Hz
• RP/high-speed pulse input point 2 frequency 
: 50Hz
• PID deviation upper limit 
: 50Hz
• Process upper limit 
• PID output upper limit 
: 50Hz
• Motor rated revolutions (motor name plate) 
: 60Hz
• VI/II input point 2 frequency 
: 60Hz
• RR/S4 input point 2 frequency 
: 60Hz
• RX input point 2 frequency 
: 60Hz
• A1 input point 2 frequency 
: 60Hz
• A2 input point 2 frequency 
: 60Hz
• RP/high-speed pulse input point 2 frequency 
: 60Hz
• PID deviation upper limit 
: 60Hz
• Process upper limit 
• PID output upper limit 
: 60Hz
• Motor rated revolutions (motor name plate) 
E-42
E6581301
Default setting
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz