INVERTER INSTRUCTION MANUAL
Compliance with CE Marking and
NOTICE
1. Make sure that this Instruction Manual is delivered to the end user of the
inverter unit.
2. Keep this manual before installing or operating the inverter unit, and
store it in a safe place for reference.
UL Standard
© Toshiba Schneider Inverter Corporation 2001
All rights reserved.
         E6580971③
VF-P7
VF-P7
200V class
400V class

Advertisement

loading

Summary of Contents for Toshiba VF-P7

  • Page 1 1. Make sure that this Instruction Manual is delivered to the end user of the inverter unit. 2. Keep this manual before installing or operating the inverter unit, and store it in a safe place for reference. © Toshiba Schneider Inverter Corporation 2001 All rights reserved.
  • Page 2                E6580971③ INDEX 1.Compliance with CE Marking ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ P2   1.1.Abstract ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ ・ P2  ...
  • Page 3                E6580971③ 1.Compliance with CE Marking 1.1. Abstract In Europe, EMC directive is enforced starting 1 Jan. of 1996, and Low Voltage Directive starting 1 Jan. of 1997. The display of CE mark that demonstrates that products imported to European Union conform to these directives is required. Inverter itself cannot function alone, but is de-signed as a component in order to control machines or equipment which includes that inverter installed in a cubicle.
  • Page 4: Emc Directive

    A machine which consists of an inverter and a motor is an object of CE marking. The EMC directive includes the emission section and the immunity section. VF-P7 can conform to EMC directive by means of installing the recommended EMI noise filter to the input side, and wiring properly.
  • Page 5                E6580971③ 1.3. Compliance with EMC directive (1) Recommended EMI noise filters(refer to Table 2) should be installed to the input. These can reduce the conducted and radiated noise. Table 2. Recommended EMI filter selection 《3-phase 200V class》 《3-phase 400V class》 Type form Filter type Type form...
  • Page 6                E6580971③   【Ex. Countermeasure – main circuit wiring】 Inverter panel (metal) FILTER R S T U V W E Separate input outputs cables. Do not run input cables along- side output cables. Do not bundle input and output cables. Note 1) Refer to P.6.
  • Page 7                E6580971③      Note 1)   Process as shown below. Shielded cable Strip the coating of the cable and fix the shielded part to the metal plate using a metal fitting. Fig. 2     【Operating with external signals】        To operate with external signals, process as following figures.      ...
  • Page 8: Low Voltage Directive

             E6580971③ 1.4. Low voltage directive Inverter itself is an object of the CE marking. The Low Voltage Directive defines the safety of the electric equipment. VF-P7 series conform to the Low Voltage directive based on EN50178. Normative standard : EN50178/Electronic equipment for use in power installation Pollution degree :2(5.2.15.2)
  • Page 9  1.5. Compliance with Low voltage directive Please carry out the below mentioned countermeasures for the Low Voltage Directive in case of using VF-P7 as components of your products. (1) Inverter should be installed in a panel. Pay attention to wiring openings, so that it should prevent someone from touching live parts through the opening in case of maintenance.
  • Page 10: Compliance With Ul Standard

    The VF-P7 models conform to the UL Standard have the UL/CUL mark on the nameplate. 2.1. Compliance with Installation The VF-P7 Inverter must be installed in a panel, and used within the maximum surrounding air temperature 50 degrees. 2.2. Compliance with Connection...
  • Page 11                E6580971③ Table.4 Wire gauge Wire gauge AWG (mm ) Inverter Input/output Control power Grounding terminal type-form terminals supply terminals VFP7-2185P 4 (21.2) 14 (2.1) 4 (21.2) VFP7-2220P 2 (33.6) 14 (2.1) 4 (21.2) VFP7-2300P 14 (2.1) 2 (33.6) 2/0 (67.4) VFP7-2370P 14 (2.1) 2 (33.6) 2/0 (67.4)...
  • Page 12                E6580971③ Table. 5 Type-form of closed-loop terminals and crimping tools Type-form of closed-loop terminal Crimping tools Air- Hand Hydraulic (mm2) pressure screw screw screw screw screw screw screw Tools tools tools YHT- BCT- 14 (2.1) R2-4 ---- ---- ---- ---- ---- YA-4...