Step 5: Provision Area Devices - Cooper WaveLinx Lite User And Programming Manual

Table of Contents

Advertisement

User Manual: WaveLinx Lite (4.0)

Step 5: Provision Area Devices

Provisioning steps, options and screens will be slightly different depending on whether the area is a networked area or a standalone area. Refer
to the steps in the section that is appropriate for the type of area being provisioned.
Networked Area Provisioning
Once the zones and occupancy sets are defined and assigned, provision the devices in the area.
Internet connection is not necessary but connection to the WaveLinx Lite device/network is required. The mobile device will need to be in range
and as close as possible (within 60 feet) to the WaveLinx Lite devices being provisioned.
Additional Tools
WaveLinx Pro IR Remote (ACC-P-RT)
Required:
63
If using the WaveLinx Pro IR Remote:
• Only the 'Rev ID' button will be used. No other buttons will
function in the WaveLinx Lite system.
• Make certain that the fixture/sensor is powered.
• Stand directly below the fixture and point the IR remote at
the sensor lens.
• For standard ceiling height mounted fixtures, use the IR
remote within 14 feet (4.27m) of the fixture. With sensors
mounted less than 4 feet (1.22m) apart, there is a
possibility that the remote signal will be received by both
sensors.
• For high mount industrial or outdoor fixtures, use the IR
remote within 25 feet (7.62m) of the fixture. With high
mount sensors mounted less than 8 feet (2.44m) apart,
there is a possibility that the remote signal will be
received by both sensors.
Begin the Provisioning Process:
Ensure that the mobile device's Bluetooth is turned on.
1: With the mobile device, stand in the selected area, standing within range of the WaveLinx Lite devices to be provisioned (within 60 feet).
2: Verify that all the area's WaveLinx Lite devices are displaying the correct out-of-the box and LED behavior for an unprovisioned device as
described on the device's reference sheet in the "WaveLinx Lite Device Reference Sheets" section beginning on page 9.
3: In the site list, select a site.
4: In the area list, select an area.
Select the site
63
If unable to use the WaveLinx Pro IR Remote to identify the fixture mounted sensors or tilemount sensors at this site, follow the procedures in the "Identify and Provision Line
Voltage Powered Wallstations" section that follows. The procedures described will also work for fixture mounted and tilemount sensors.
Select the area