User Manual: WaveLinx Lite (4.0)
Use Occupancy Sensor Test Mode in a Standalone Area
An occupancy sensor may be placed into a temporary test mode to verify sensor response. If test
'Occupancy...' tab
mode is activated, this sensor will be placed in test mode for 10 minutes. The sensor operates
with a 10 second hold time. Test mode will automatically revert to normal operation after 10
minutes or may be manually disabled through the mobile application.
To test an occupancy sensor, test during a time when there is little motion occurring in the area.
Access the device 'Occupancy...' tab and slide the test switch to the ON position.
If lighting is ON, stand still. Lighting should transition to the unoccupied level after 10 seconds of
no activity on any sensor. Once lighting goes to the unoccupied level, move to verify that the
lighting goes back to the occupied level.
Repeat this process for each sensor location to verify individual sensor operation. If the sensor
sensitivity needs to be adjusted, see page 126 for further details.
Test mode
128
www.cooperlighting.com