Review/Adjust Individual Occupancy Sensor Settings In A Standalone Area - Cooper WaveLinx Lite User And Programming Manual

Table of Contents

Advertisement

6: Adjust the desired setting per the chart below, and then tap 'Save'.

Review/Adjust Individual Occupancy Sensor Settings in a Standalone Area

Additional details regarding the sensor can be seen in the 'Device Details' page.
To access the device's occupancy sensor details page:
1: Ensure that the mobile device Bluetooth is turned on, and then open the WaveLinx Lite Mobile Application.
2: In the site list, select a site and then in the area list, select the standalone area.
86
If occupancy is sensed in the 30 seconds after an unoccupied command is issued (grace period), the device will resume the previous light level. If outside of the grace
period, the light level issued when occupied will be as defined for the occupied command. Devices with older firmware may not observe the 30 second grace period.
126
www.cooperlighting.com
Setting
Default
Current Status
N/A
Hold Time
20 Minutes
Energy Saver
Enabled
Mode
Energy Saver
10 Minutes
Hold Time
Occupied Level
Level 100%
Energy Level
Level 50%
Unoccupied
Level 0%
Level
Description
Displays the status of the sensor, either occupied or
unoccupied.
Note: Status reflected does not include the hold time delay. It reflects if
actual motion activity was occurring at the time the status last loaded.
The hold time determines how long the fixture will wait after
the sensor no longer detects occupancy before going to the
defined unoccupied level. The hold time can be defined from 1
to 40 minutes by selecting from the drop-down options, or by
typing in the desired hold time.
Use the slider to enable or disable energy saver mode for a
dimmable load.
• If disabled, once the space is no longer occupied and the
hold time expires, the lighting will transition from the current
level to the unoccupied state with no interim light level.
• If enabled, once the space is no longer occupied, the hold
time countdown and energy saver mode countdown begin.
Dimmable lighting will go to the defined energy saver level
after the energy saver mode time defined.
If the space remains unoccupied and the hold time expires,
the lighting will go to the unoccupied level.
Example: If the hold time is 20 minutes, and the Energy Saver Mode
time is set for 10 minutes, the Energy Saver level occurs after 10
minutes of no occupancy. After an additional 10 minutes, the
unoccupied level is issued.
If Energy Saver Mode is enabled, the energy saver hold time
setting defines the amount of time that the sensor will wait
once the area is unoccupied before transitioning dimmable
light level to the level defined for the Energy State.
This is the light level that will be issued when motion is initially
detected.
Use the slider bar, raise lower controls, or text box
86
entry to adjust the level. The occupied level cannot be lower
than the energy level.
This is the light level that will be issued to a dimmable load if
the energy saver mode has been enabled and the energy hold
time has expired. Use the slider bar, raise lower controls, or
text box entry to adjust the level. The energy level cannot
higher than the occupied level.
This is the light level that will be issued when the hold time
expires. Use the slider bar, raise lower controls, or text box
entry to adjust the level. The unoccupied level cannot be higher
than the energy level.
User Manual: WaveLinx Lite (4.0)

Advertisement

Table of Contents
loading

Table of Contents