Update Device Firmware - Cooper WaveLinx Lite User And Programming Manual

Table of Contents

Advertisement

To delete the local site database:
1: Ensure that the mobile device has internet access and then launch the WaveLinx Lite Mobile Application.
2: Once logged in, review the site sync status:
• Ready: proceed to the next step
• Submit Changes: make certain that all changes are submitted to the cloud before proceeding.
• Update Pending: The cloud database is newer than the local database. As the local database is being deleted, no action is necessary.
Proceed to the next step.
• Merge Conflict: Refer to "Merge Conflict Status" on page 150 for specific instructions on how to proceed.
3: Next, tap the more icon ' ' in the site's row.
4: Select the option to 'Delete Local Copy' and then, when prompted, confirm the deletion.
The site local database will be removed. The site name will be moved into the 'Available Sites' section where it can be restored in the future
from the cloud database as needed.
Verify site sync
status

Update Device Firmware

At times, it may be necessary to update devices with new firmware. It is important that firmware is up to date to ensure functionality and
security. A direct Bluetooth connection from the mobile device to the WaveLinx Lite device is required for firmware updates. The update will not
be processed through the Bluetooth mesh network. Except for the Battery Powered Wallstation, it is possible to update devices of the same
type at the same time if they are within range of the mobile device. Devices do not have to be provisioned to respond to a firmware update if
they are within the mobile device's Bluetooth range.
During Firmware Updates:
• Device configuration will be retained during a firmware update.
• Devices will remain in the last commanded state during the firmware update, re-evaluating after the firmware update is complete. If device
contains an occupancy sensor, the occupancy sensor may issue an occupied command when device resets. If the area is not occupied,
the device will follow its programmed hold time sequence to enter the unoccupied state.
• If a firmware update fails, the device will remain operational with the original device firmware.
Note: Some devices may also support conversion from WaveLinx Lite to WaveLinx Pro operation. Contact technical support for details.