Setting Routing Tables
7-4-2

Editing Local Network Tables

7-4-3

Editing Relay Network Tables

Use the routing table editing function on the Programming Device to edit the
local network table as shown on the screen given below.
Local network:
Address 1 through 127 for the network connected to the Communications Unit
SIOU Unit No.:
Unit number of the Communications Unit. (CS-series, CVM1, or CV-series: 0
to 15) Set the unit number of all Communications Units (SYSMAC NET Link
Units, SYSMAC Link Units and Controller Link Units) as well as the address of
network connected to it.
Be sure to set the same address for each network when setting routing tables
(local and relay network tables) in multiple PLCs.
Use the routing table editing function on the Programming Device to edit the
local network table as shown on the screen given below.
End network:
Network address of the end network (1 through 127)
Relay network:
Network address of the first relay point on the way to the end network (1
through 127)
Relay node:
Node address of the first relay point on the way to the end network
(SYSMAC NET: 1 through 126, SYSMAC LINK: 1 through 62, and Controller
Link (Wired or Optical Bus): 1 through 32, Ethernet: 1 through 127)
Set all networks not directly connected to the PLC.
Section 7-4