Omron SYSMAC CS1W-CLK13 Operation Manual page 271

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Status Area and Troubleshooting
Network Participation Status: CIO 1500 + 25 x (Unit No.) + 2 to + 5
Local Data Link Participation Status: CIO 1500 + 25 x (Unit No.) + 6
Note
248
−: Not used
The numbers in the squares correspond to node addresses.
The bit status indicates each node's participation status as follows:
0: Not part of the network
1: Part of the network
Note When the local node is not part of the network, the local
node's participation status bit will be 0. The participa-
tion status of other nodes will not be reliable in this
case.
15 14 13 12 11 10
9
8
7
0
0
0
0
0
0
0
0
Data link mode
0: Manual setting
1: Automatic setting
1: Local node data link participating
0: Local node data link not participating or data link inactive
Data link status is valid only when the local node is participating in the data
link. Confirm that the Local Data Link Participation Flag is ON before referenc-
ing the data link status.
6
5
4
3
2
1
0
−: Not used
0
0
0
0
0
0
Allocation for automatic setting
00: Equality layout
01: 1:N allocation, common type
10: 1:N allocation, 1 to 1 type
11: 1:N allocation, chain type
Section 10-2