Using A Programming Device Or The User Program - Omron SYSMAC CS1W-CLK13 Operation Manual

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Starting and Stopping Data Links
5-3-1

Using a Programming Device or the User Program

Note
CS-series Start Bit
15 14 13 12 11 10 9
-
-
0
Word N
N: D30000 + 100 × (unit number)
0: Always set to 0.
-: Other settings
CVM1 and CV-series Start Bit
15 14 13 12 11 10 9
-
-
0
Word N
N: D2000 + 100 × (unit number)
0: Always set to 0.
-:
Other settings
Note
128
2. In CS1D Systems with Controller Link Units used in duplex operation, set
the duplex node as a startup node for data links (Data Link Start/Stop Bit
in the CS1D System CPU Unit is turned ON). If the duplex node is not set
to be a startup node for data links (Data Link Start/Stop Bit in the CS1D
System CPU Unit is OFF), and the relevant node is operating as a polling
node, the network's data links may stop if an ACT/STB (active/standby)
switchover error occurs.
Set the software switch (AR or DM Start Bit) in the PLC to ON using a Pro-
gramming Device or from the user program.
Programming Device
The data links will start when the Start Bit changes from OFF to ON or is
already ON when power is turned on. The data links will stop when the Start
Bit changes from ON to OFF.
The data in the AR and DM Areas is retained when power is turned off. There-
fore, by setting in the AR and DM Areas can be made in advance to start data
links as soon as power is turned on.
It is recommended to set the Start Bit to ON in multiple nodes that are partici-
pating in the data link so that the data links will start even if the startup node is
down. The same data link settings must be set in these nodes for automati-
cally set data links.
8
7
6
5
0
0
0
-
-
-
-
-
8
7
6
5
0
0
0
-
-
-
0
-
In CS1D Systems with Controller Link Units used in duplex operation, set the
duplex node as a startup node for data links (Data Link Start/Stop Bit in the
CS1D System CPU Unit is turned ON). If the duplex node is not set to be a
Startup node
CS-series PLCs
Turn ON the Start Bit in D30000 + 100 × N.
(N: unit number)
CX-Programmer
CVM1 and CV-series PLCs
Turn ON the Start Bit in D2000 + 100 × N.
(N: unit number)
4
3
2
1
0
-
0
0
0
Data link Start Bit
Start: Changed from OFF to ON or set to ON
when power is turned on
Stop: Changed from ON to OFF
4
3
2
1
0
-
0
0
0
Data link Start Bit
Start: Changed from OFF to ON or set to ON
when power is turned on
Stop: Changed from ON to OFF
Section 5-3
User program
Controller Link