Routing Table Setting Procedure; Editing Local Network Tables - Omron SYSMAC CS1W-CLK11 Operation Manual

Table of Contents

Advertisement

Setting Routing Tables
7-4-1

Routing Table Setting Procedure

1,2,3...
7-4-2

Editing Local Network Tables

Note
Routing tables are required if any of the CVM1 or CV-series CPU Units in
the network have been manufactured on or before April 1996.
Lot No.: @ @ 4
6 ..... Manufactured in April 1996
5. Routing tables are handled differently with C200HX/HG/HE PCs depend-
ing on whether they are used in a Controller Link or SYSMAC NET Net-
work. Be sure to register both Controller Link and SYSMAC NET routing
tables when SYSMAC NET Link Units are installed at the same time. See
the SYSMAC NET Link Unit Operation Manual (W114) for further details.
The procedure for setting routing tables is described below.
1. Edit the local network table.
2. Edit the relay network table.
3. Save the routing tables.
4. Connect the Programming Device to a PC.
5. Turn ON the Routing Table Enable Bit for C200HX/HG/HE and CQM1H-se-
ries PCs only.
6. Transfer the routing tables.
Use the routing table editing function on the Programming Device to edit the
local network table as shown on the screen given below.
Local network:
Address 1 through 127 for the network connected to the Communications Unit
SIOU Unit No.:
Unit number of the Communications Unit (operating level for C200HX/HG/HE
PCs; always 0 for CQM1H-series Units). (CS/CJ-series, CVM1, or CV-series:
0 to 15, C200HX/HG/HE: 0,1, CQM1H-series: 0) Set the unit number of all
Communications Units (SYSMAC NET Link Units, SYSMAC Link Units and
Controller Link Units) as well as the address of network connected to it.
Be sure to set the same address for each network when setting routing tables
(local and relay network tables) in multiple PCs.
Indicates the last digit of the manufacturing
year. In this example, the year is 1996.
Indicates the month of manufacture. October,
November, and December are indicated by x, y,
and z respectively. In this example, the month is
April.
Repeat the editing and
saving steps for all
nodes set with the rout-
ing tables.
Section 7-4
185