Omron SYSMAC CS1W-CLK13 Operation Manual page 288

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Error Log
Error
Contents
code
0115
Transmission failed; redundant
Hex
I/O allocations
0116
Transmission failed; CPU Bus
Hex
Unit error
0117
Internal buffer full
Hex
0118
Illegal packet discarded
Hex
0203
EEPROM error
Hex
0206
Number of participating nodes
Hex
decreased (local node still partic-
ipating)
0207
Number of participating nodes
Hex
decreased (local node not partic-
ipating)
0208
Polling node changed
Hex
0209
Inconsistent network parameter
Hex
020C
Time out with token
Hex
0210
Communications controller send
Hex
error
0211
Duplicate address error
Hex
0214
Node address setting error
Hex
Detail code
1st byte
2nd byte
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network
address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
01 Hex:
01 Hex:
Read error
Data link
02: Hex:
tables
Write error
02 Hex: Net-
work param-
eters
03 Hex:
Routing
tables
Network
Number of
parameters
non-partici-
maximum
pating nodes
node
address
Address of
Address of
previous
new polling
polling node
node
00 Hex
Address of
polling node
00 Hex
Error status
(See note 3.)
00 Hex
Error status
(See note 3.)
00 Hex
Local node
address
Not specified
Correction
Written to
EEPROM
Check unit numbers
No
for redundancy
within the same PLC.
Check Unit and cable
No
connections and
clear error.
Increase number of
No
retries or reconfig-
ure system to distrib-
ute load.
Check for nodes
Yes
sending illegal pack-
ets.
For CVM1 and CV-
Yes
series PLCs, check
that the PLC is not
protected.
Remake and set the
relevant data. If the
error occurs again for
the CVM1 and CV-
series, replace the
CPU Unit.
Check network
No
parameters, node
(See note
participation, cables,
4.)
and terminating
No
resistance.
(See note
4.)
Check previous poll-
No
ing node.
(See note
4.)
Using the Controller
Yes
Link Support Soft-
ware, check network
parameters.
Check network
No
parameters, node
participation, cables,
and terminating
resistance.
Replace the Control-
Yes
ler Link Unit.
Reset so that each
No
node address is
(See note
used only once
4.)
within the same Net-
work.
Check the node
Yes
address settings and
correct them.
Section 10-3
Applicable
PLC
CV, CS
CV, CS
CV, CS
CV, CS
CV
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CS
265