Online Replacement; Duplex Unit System Configuration; System Configuration - Omron SYSMAC CS1W-CLK13 Operation Manual

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Duplex Unit System Configuration

8-1-2

Online Replacement

Note
8-2
Duplex Unit System Configuration
8-2-1

System Configuration

Backup
power supply
(24 VDC)
202
If there is an active/standby switchover due to one the reasons above, a
duplex communications error is detected at the CPU Unit, and the corre-
sponding Duplex Communications Switched Flag (A43600 to A43615: bits
00 to 15 correspond to the unit number) turns ON. The reason for the
switch is recorded in the Duplex Communications Switch Cause Flags
(A042 to A049).
• If an error is detected in the standby Controller Link Unit by self-diagnosis,
a duplex communications error is detected at the CPU Unit, and the corre-
sponding Duplex Communications Standby Unit Error Flag (A43700 to
A43715: bits 00 to 15 correspond to the unit number) turns ON. The
active Unit will continue to operate normally and communications will con-
tinue. There will be no active/standby switchover.
In CS1D Systems, a Controller Link Units with an error can be replaced with-
out turning OFF the PLC's power supply (online replacement). For details on
the procedure for online replacement, refer to page 294.
Replacing a standby Controller Link Unit has no effect on communications.
When an active Controller Link Unit is replaced, there is an active/standby
switchover. The relevant node will temporarily leave and then re-enter the net-
work and communications operations will be temporarily stopped. For details
on the time required for communications to resume, refer to 8-5 Switching
Time for Duplex Units.
The online replacement procedure is performed from a Programming Con-
sole.
Duplex Controller Link Unit
(token ring mode)
PLC CS1D
C
C
P
P
U
U
Optical fiber cable
(ring connection)
C
C
P
P
U
U
PLC CS1D
Duplex Controller Link Unit
(token ring mode)
The Controller Link Units can be duplexed by combining a CS1D System and
the following Duplex-compatible Controller Link Units.
Unit
Duplex-compatible
CS1W-CLK13, CS1W-CLK53,
Controller Link Unit
CS1W-CLK12-V1, CS1W-CLK52-V1
Duplex Controller Link Unit
(token ring mode)
PLC CS1D
C
C
P
P
U
U
C
C
P
P
U
U
PLC CS1D
Duplex Controller Link Unit
(token ring mode)
Model
Section 8-2

Advertisement

Table of Contents
loading