Omron SYSMAC CS1W-CLK13 Operation Manual page 309

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Troubleshooting for Duplex Communications Units
Troubleshooting for Errors at Startup
Active Unit
Standby Unit
RUN
ERC
RUN
Lit
Not lit
Flashing Not lit
Not lit
Not lit
Not lit
Lit
Not lit
Lit
Not lit
Not lit
Flashing Not lit
(ERH is
lit)
Lit
Not lit
Not lit
Lit
Not lit
Not lit
(ERH is
lit)
Lit
Not lit
Not lit
(ERH is
lit)
286
Status area
(Auxiliary Area)
ERC
---
Not lit
---
---
---
CPU Bus Unit Error Flag
(A40207)
I/O bus error B:
I/O Bus Error Flag
(A40114)
I/O Bus Error Rack
Number (0B Hex is
stored in bits 8 to 15 of
A404)
Not lit
(CPU on standby)
Duplex Communications
Setting Error Flags
(A435)
CPU Bus Unit Setting
Error Flag (A40203)
Not lit
Duplex Communications
(ERH is
Setting Error Flags
lit)
(A435)
CPU Bus Unit Setting
Error Flag (A40203)
Not lit
CPU Bus Unit
Duplication Error Flag
(ERH is
(A40113)
lit)
Not lit
Duplex Communications
Setting Error Flags
(A435)
CPU Bus Unit Setting
Error Flag (A40203)
CPU Bus Unit Setting
Error Flag (A40207)
Probable cause
Both the active and
---
standby Units are
operating normally.
Power is not being
Check the power supply
supplied correctly to the
voltage and supply at the
PLC.
recommended voltage.
The Power Supply Unit
Use CS1D Power Supply
is not a CS1D Power
Units for CS1D Systems.
Supply Unit.
The Controller Link Unit
Secure the Controller
has become loose.
Link Unit firmly.
There were errors in
If the same problem
both active and standby
occurs when the Units
Units.
are mounted on another
PLC, replace them.
The wrong Expansion
Replace the Expansion
Backplane is connected.
Backplane with a CS1D
Expansion Backplane
(supports online Unit
replacement).
4 or more pairs of
The maximum number of
Communications Units
pairs of Communications
are set for duplex
Units mounted on 1
operation.
CS1D PLC that can be
set for duplex operation
is 3.
The active Controller
Set the active Controller
Link Unit's unit number is
Link Unit's unit number to
set incorrectly.
the same number as the
standby Unit and reset
the power.
The active Controller
Mount a duplex-
Link Unit does not
compatible Controller
support duplex
Link Unit (CS1W-CLK13,
operation.
CS1W-CLK12-V1,
CS1W-CLK53, or CS1W-
CLK52-V1).
The standby Controller
Set the standby
Link Unit's unit number is
Controller Link Unit's unit
set incorrectly.
number to the same
number as the active Unit
and reset the power.
The duplex settings in
Make the duplex settings
the PLC Setup have not
for the relevant Unit
been made.
under Communication
Unit Duplex Setting in the
PLC Setup using CX-
Programmer.
The active Controller
Mount a duplex-
Link Unit does not
compatible Controller
support duplex
Link Unit (CS1W-CLK13,
operation.
CS1W-CLK12-V1,
CS1W-CLK53, or CS1W-
CLK52-V1).
Section 10-6
Probable remedy