Omron SYSMAC CS1W-CLK13 Operation Manual page 188

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Commands and Responses for Controller Link Units
Response Block
06
01
Command
Response code
code
Operating status
Parameters
1: Error log exists
1: Data link error stop
1: Controller transmitter error
Note
00
00
00
Status 1
Status 3
Status 2
Status 4
Total 6 bytes
Operating status (response): The operating status of the data links as fol-
lows:
00 (Hex): Data links inactive.
01 (Hex): Data links active.
02 (Hex): Local data links not active. (The data links are active in the net-
work, but the local node is not participating.)
Status 1, Status 4, Status 6 (response): Not used by the Controller Link
Unit. Always set to 00 (Hex).
Status 2 (response): The Controller Link Network's transmission speed and
the status of the Controller Link Unit's backup power supply is returned with
the following configuration.
Bit
Transmission speed:
1 Hex: 2 Mbps
Status 3 (response): Error information. The configuration is as follows:
7
6 5 4 3 2 1 0
Bit
0
1. This bit may be 1 if an Optical Ring Controller Link Unit is mistakenly con-
nected to an Optical Bus Network or SYSMAC LINK Network.
2. A network parameter error occurs if the registered network parameter con-
tents do not match the actual network parameter contents after the power
is turned on. The system, however, will not stop. When a network param-
eter error occurs, the actual network parameter contents are automatically
registered to that Unit.
Status 5 (response): Error information related to the Unit and the PLC. The
configuration is as follows:
1: EEPROM error
1: PLC system setting error
A network parameter error, data link table error, or routing table error occurs if
an error is discovered when the parameters and tables are checked at power
up.
00
00
Status 5
Count 1
Status 6
Total 8 bytes
0: Backup power being supplied
1: Backup power not being supplied
1: Node address setting error
1: Duplicate node address setting error (See note 1.)
1: Network parameter error (See note 2.)
1: Controller hardware error
Bit
7
6 5 4 3 2 1 0
0
0
0
Section 6-5
00
8 bytes
Count 8 Active node list
1: Network parameter error
1: Data link table error
1: Routing table error
165