Memory Areas
Parameters for Automatically Setting Data Links: DM 2000 + 100 x (Unit No.) + 1 to + 11 (See page 123.)
15
Area 1 data link start word (BCD)
+1
+2
Area 1 type
Number of send words per node of area 1 (BCD)
+3
+4
Rightmost 4 digits of data link start word of area 2(BCD)
+5
Area 2 type
+6
Number of send words per node of area 2 (BCD)
First data link status word (BCD)
+7
15 14 13 12 11 10 9
+8
16 15 14 13 12 11 10 9
+9
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
+10
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
− 62 61 60 59 58 57 56 55 54 53 52 51 50 49
+11
−: Not used.
Note N+10 and N+11 (node addresses 33 to 62) cannot be used in Optical Bus Systems.
322
8
7
00
Leftmost digit of data link start word of area
2 (BCD)
8
7
6
5
4
8
7
6
5
BCD: Set the value as binary-coded decimal.
0
3
2
1
0
Nodes to participate in the data links
4
3
2
1
The numbers indicate node numbers.
The value assigned indicates whether the
node is to participate in the data links.
Participate: 1
Not participate: 0
Appendix A